Combustible gas

Hand-held Combustible gas detector
[MA-2510]
  • Compact and Lightweight
  • Low power consumption sensor
  • Analog display shows LEL or concentration (%)
  • Measurement of combustible gases other than methane
MA-2510 Specifications
Measurement range: 0-25%LEL, 0-100%LEL
Measurement method: Catalytic combustion gas sensor
Sampling method: Diaphragm pump
Display: Analog metre (backlit)
Indicating accuracy: +/-5% at full scale at time of calibration
Alarm threshold and signal: > 20%LEL
Alarm threshold and signal: intermittent sound and blinking light
Power source: Three size C manganese dry cell batteries for 4 hours of operation (without alarm signal being emitted)
Three size C alkaline dry cell batteries for 8 hours of operation (without alarm signal being emitted)
Dimensions: 151(W) x 71(D) x 115(H)
Weight: 1.1kg
Explosion proofing: Certified by Japan Ministry of Health, Labour and Welfare (Class id3aG3 No.T62339)
Return to previous viewReturn to listGo to top of page

Hand-held methane gas detector
[MAM-2510]
  • Compact and lightweight
  • Low power consumption sensor
  • Analog display shows LEL or concentration (%)
  • For exclusive measurement of methane gas only
MAM-2510 Specifications
Measurement range: 0 - 25%LEL, 0 - 100%LEL
Measurement method: Catalytic combustion gas sensor
Sampling method: Diaphragm pump
Display: Analog metre (backlit)
Indicating accuracy: +/- 5% of full scale
Alarm threshold and signal: 20% LEL
Alarm threshold and signal: Intermittent sound and blinking alarm light
Power source: Three size C manganese dry cell batteries for 4 hours of operation (without alarm signal being emitted)
Three size C alkaline dry cell batteries for 8 hours of operation (without alarm signal being emitted)
Dimensions: 151(W) x 71(D) x 115(H)
Weight: 1.1kg
Explosion proofing: Certified by Japan Ministry of Health, Labour and Welfare (Class id3aG3 No.T62339)
Return to previous viewReturn to listGo to top of page

Hand-held methane detector
[MA-0510]
  • Compact and lightweight
  • Low power consumption sensor
  • Analog display shows accurate measurement with ppm unit
  • Measurement of combustible gases other than methane
MA-0510 Specifications
Measurement range: 0 -500 ppm, 0 -1000 ppm
Measurement method: Catalytic combustion gas sensor
Sampling method: Diaphragm pump
Display: Analog metre (backlit)
Indicating accuracy: +/- 5% of full scale
Alarm threshold and signal: Optional setting possible at 200 ppm or above
Alarm threshold and signal: Intermittent sound and blinking alarm light
Power source: Three size C manganese dry cell batteries for 4 hours of operation (without alarm signal being emitted)
Three size C alkaline dry cell batteries for 8 hours of operation (without alarm signal being emitted)
Dimensions: 151(W) x 71(D) x 115(H)
Weight: 1.1kg
Explosion proof: Certified by Japan Ministry of Health, Labour and Welfare (Class id3aG3 Certification No.T62339)
Return to previous viewReturn to listGo to top of page